05-A · Who touches it
A device for accredited hands only
Not a do-it-yourself device
Only licensed plumbers with backflow accreditation from a registered training organisation may inspect, commission and test medium and high hazard backflow devices, and a licensed plumber must install the device. Sydney Water keeps a search of accredited backflow plumbers.
The household part is smaller. Sydney Water names two ways contaminants get into drinking water through a cross connection, an unauthorised link between water that should be kept apart: faulty plumbing, and hoses left submerged in buckets, tanks or pools. It also says backflow is more likely when the main loses pressure, during a main break for example, or when the pressure on a property is higher than in the main, such as while a pump is running.
05-B · Fire services
Sprinklers, hydrants and hose reels
For buildings with fire services, Sydney Water’s rules are specific:
05-C · On the bill
The backflow fees on a Sydney Water bill
Only a property with a testable containment device pays these; a typical house does not.
| Charge | When it applies | 2026–27 |
|---|---|---|
| Backflow administration fee | Every quarter, one per property, toward Sydney Water’s backflow prevention program. | $11.05 a quarter |
| Annual test fee | If the yearly test is not done, Sydney Water may send an accredited plumber to test, charged for each device on the next bill. | $553.12 including GST |
| No access fee | If that plumber cannot test for reasons attributable to you, such as refused access or locked premises. | $431.68 including GST |
One more thing the device changes: Sydney Water’s free repair of the pipe between its main and your meter does not cover a failure that relates to a backflow prevention device.
05-D · Inside the building
Specification 41, and where a device can sit
Inside the building, the Plumbing Code of Australia lists common hazard scenarios in its Specification 41, and each needs a device suited to its hazard rating. Where a hazard is not listed, the plumber either submits a Performance Solution or fits a default high hazard device such as a reduced pressure zone device, a registered break tank or a registered air gap. One NSW variation is about rainwater tanks: for a Class 1 building, drinking and non-drinking water must be zone protected from a rainwater tank with a non-testable device.
05-E · The yearly round
From the first assessment to the yearly reminder
- 1
Assess
An accredited backflow plumber works out the site’s hazard rating, and it is worked out again whenever what happens on the site changes. More than one connection to the main means more than one containment device. The device for each rating is set out on Sydney Water’s page.
- 2
Install and register
It falls to the owner to see that the plumber fits the right device, tests it and registers it. A newly fitted device is tested by a backflow-accredited plumber and registered straight away.
- 3
Lodge the report
The plumber has 2 days from the test to lodge the results. Ask for your own copy of the report.
- 4
Every year
Medium and high hazard devices are tested when they are fitted and then once a year. Sydney Water keeps a register of installed testable devices and reminds you when a test falls due.
Sydney Water also audits a sample of installations, and an owner who ignores its notices about a device that does not comply can face further action; its backflow page lists what it may do.